[alpus_aprs_ai_summary]

Description

Technical Specifications

Output

Max Configurable Power (Watts)

40.0kWatts / 40.0kVA
Output Voltage Distortion

Less than 3 %
Output Frequency (sync to mains)

50 Hz +/- 0.1 % For 50 Hz nominal Unsynchronised, 50 Hz Sync to mains, 60 Hz +/- 0.1 % For 60 Hz nominal Unsynchronised, 60 Hz Sync to mains
Other Output Voltages

380 V, 415 V
Load Crest Factor

2.5
Waveform type

Sine wave
Overload Operation

10 minutes at 125% and 60 seconds at 150%
Output Voltage THD

< 1% linear load and < 3% non-linear load
Output Voltage Tolerance

+/-1% after 50ms
Bypass

Built-in static bypass

Input

Input frequency

40 – 70 Hz
Input voltage range for main operations

340 – 460 (400 V)V
Input Total Harmonic Distortion

Less than 3 % for full load
Other Input Voltages

380 V, 415 V
Maximum Short Circuit Withstand (Icw)

65.0kAmps
Input Power Factor at Full Load

0.99

Batteries & Runtime

Battery type

External battery system, Li-Ion (Lithium-Ion), VRLA
Nominal Battery Voltage

384…576 V DC
End of Discharge Maximum Battery Current

136.0A
End of Discharge Battery Voltage

307 V DC

Communications & Management

Interface Port(s)

GVS_Parallel, GVS_WideUPS_AirFilter, GVS_WideUPSMBC_SeismicKit
Control panel

Touch screen LCD user interface
Audible Alarm

Audible and visible alarms prioritized by severity
Available SmartSlot™ Interface Quantity

1

Physical

Maximum Height

1485MM, 148.5CM
Maximum Width

521MM, 52.1CM
Maximum Depth

847MM, 84.7CM
Net Weight

206.0KG
Shipping weight

235.0KG
Shipping Height

1680MM, 168.0CM
Shipping Width

640MM, 64.0CM
Shipping Depth

990MM, 99.0CM
Color

White

Environmental

Operating Temperature

0 – 40 °C
Operating Relative Humidity

0 – 95 (Non-condensing) %
Operating Elevation

0 – 1000.05meters
Storage Temperature

-25 – 55 °C
Storage Relative Humidity

10 – 80 (Non-condensing) %
Storage Elevation

0 – 15240meters
Audible noise at 1 meter from surface of unit

65.0dBA
Online thermal dissipation

3845.0BTU/hr
Protection Class

IP21

Conformance

Approvals

CSA C22.2 No 107.3, EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, FCC part 15 class A, IEC 60721-4-2 level 2M2, UL 1778 5th edition
Standard warranty

1 year on-site repair or replace with factory authorized Start-Up

Sustainable Offer Status

RoHS

Compliant
PEP

Available in Documentation tab
Other Environmental Compliance

China RoHS

General

Max Bypass Input Current

64.0A